Menü öffnen
Suchen
Region (de)
Products
Company
Contact
de  en  pl  fr  hr  nl  hu  it  sv  sl  cn  es

Fire protection kit S90

for HSI 150 press seal

HSS150 HSI150 HRD

Article no.: 2600030001

  • Fire protection S90 combined with HRD 150/160 press seal
  • Special assembly pockets for the assembly of pads on one side
Gastight and watertight fire barrier meeting the requirements of fire resistance class S90 in accordance with DIN 4102-9 for installation in the HSI 150 system for walls. The seal is created with the HRD press seal. The barrier is approved for use with all types of cable in walls.

Facts

Advantages:

  • Fire protection for HSI 150 cable entry
  • No additional wall attachments necessary
  • No limits on cable diameters
  • Weatherproof fire-stop pads
  • Approval for packages with HSI  150 up to 2  x  6

Scope of delivery:

  • 1 set of HVS pads for full assignment (without cable): 2x HVS-K-400, 3x HVS-K-250, 3x HVS-KB-60
  • Stainless steel clamping strap
  • Identification sign

Dimensions:

  • Wall thickness at and above: 150 mm
  • Barrier thickness: min. 280 mm
  • Maximum package size: 430 x 1270 mm (2x6)

Properties:

  • HRD 150/160 press seal for pressure-tight entry are listed under cable seals.

Tests/Standards:

  • DIBT approval Z-19.15-1906 to DIN 4102-9